Differential. The L7248 models have High Limit

Differential presets of 15°F (8°C). The L7224

models have High Limit Differential presets of 10°F

(6°C).

Figure 24: Setpoints and Differentials

Action

System Response

Thermostat

calls for heat.

Circulator starts when water temperature is

above Low Limit setting (if applicable). Boiler

temperature is checked. Burner starts when

water temperature is below High Limit setting.

Boiler exceeds

the High Limit.

Burner is turned off. Burner restarts when the

water temperature drops below the High Limit

setting minus the Differential.

Thermostat is

satisfied.

Circulator and burner turn off.

Error condition

1-5.

If an error condition is detected, all outputs ex-

cept ZC are shut down. Burner is off. Control

continues to function and restarts when error is

corrected.

During the error check sequence, the system

checks for drift in the sensor and corrosion in

the connections.

Error

condition 6.

EnviraCOM communication is not available.

Error

condition 7.

The control has reset the High Limit, Low Limit

and Differential setting to a default setting and

will continue to run at those settings.

Performance of the system will be degraded.

Error

condition 8.

If the error condition is detected, all outputs

except ZC are shut down. Burner is off. Control

continues to function and restarts when all

three user keys have been pressed longer than

60 seconds.

Table 5: L7224 / L7248 Controller

Operating Sequence

System Condition

Diagnostic Condition

Check

Action

Boiler is cold, house is

cold.

Display is OFF.

120 Vac System power.

Turn system power on.

Display is ON.

24 Vac T-T

No 24 V; replace control.

24 V present; disconnect thermostat,

short T-T.

Boiler starts, check wiring and thermostat.

120 Vac at B1-B2

• If no, replace control.

• If yes, check burner and wiring.

Refer to Err on display.

-----

Boiler is hot, house is

cold.

Display is ON.

120 Vac at C1-C2

• 120 Vac at C1-C2, check wiring

to pump.

• Wiring OK, is pump running?

• If not, replace the pump.

• If pump is running, check for

trapped air or closed zone valves

Boiler below the Low Limit tempera-

ture, wait for boiler to go above Low

Limit temperature.

-----

Boiler above LL? If yes, check for

120 Vac between ZC and L2.

• If no 120 Vac , replace control.

• If yes, check zone relays, circulators

and wiring.

Table : Trouble Shooting Guide

9. LOW LIMIT AND CIRCULATOR CONTROLLER

On a temperature rise, with the adjustable

Differential at the default setting of 10°F (6°C),

the burner circuit breaks and the circulator circuit

makes (assuming no call for heat is present) at the

Low Limit setpoint. On a temperature drop of 10°F

(6°C) below the Low Limit setpoint, the burner

circuit makes and the circulator circuit breaks. See

Figure 24.