. Two-Pipe Oil Lines

1. For two-piped systems, where more lift is required,

the two-stage fuel unit is recommended. Table

2 (single-stage) and Table 3 (two-stage) show

allowable lift and lengths of 3/8 inch and 1/2 inch

OD tubing for both suction and return lines. Refer

to Figure 21.

Figure 2: Two-Pipe Installation

Lift "H"

(See Figure 21)

Maximum Length of Tubing

"H" + "R" (See Figure 21)

3/8" OD Tubing

(3 GPH)

1/2" OD Tubing

(3 GPH)

0'

84'

100'

1'

78'

100'

2'

73'

100'

3'

68'

100'

4'

63'

100'

5'

57'

100'

6'

52'

100'

7'

47'

100'

8'

42'

100'

9'

36'

100'

10'

31'

100'

11'

26'

100'

12'

21'

83'

13'

---

62'

14'

---

41'

Lift "H"

(See Figure 21)

Maximum Length of Tubing

"H" + "R" (See Figure 21)

3/8" OD Tubing

(3 GPH)

1/2" OD Tubing

(3 GPH)

0'

93'

100'

2'

85'

100'

4'

77'

100'

6'

69'

100'

8'

60'

100'

10'

52'

100'

12'

44'

100'

14'

36'

100'

16'

27'

100'

18'

---

76'

Table 3: Two-Stage Units (3450 RPM) -

Two Pipe Systems

Table 2: Single-Stage Units (3450 RPM) -

Two Pipe Systems