Model 5600se downflow, Control start-up procedures (cont’d.) – Watts Fleck 5600 Plastic Valve User Manual
Page 7

Model 5600SE Downflow
7
Control Start-Up Procedures (Cont’d.)
Start an Extra Regeneration Cycle
Push the Extra Regeneration button to start an extra regeneration tonight. Push and hold the Extra Regeneration button
for 5 seconds to start an Extra Regeneration immediately.
Set Control Programming
1. Push and hold both the Set Up and Set Down buttons for 5 seconds.
2. Set the Treated Water Capacity. Using the Set Up or Set Down buttons, set the amount of treated water to flow through
the unit before a regeneration is required.
3. Push the Extra Regeneration button.
4. Set the Regeneration Time. Use the Set Up or Set Down buttons to set the desired time of day for regeneration to occur.
Figure 4: Set Treated Water Capacity
Figure 5: Set Regeneration Time
650 gallon capacity
2:00 A.M.
Regeneration Time