Sending the configuration message to register 13 – Banner SureCross DX80 Wireless M-GAGE Node User Manual
Page 7

P/N 131598 rev. F
7
Banner Engineering Corp. • Minneapolis, MN U.S.A
www.bannerengineering.com • Tel: 763.544.3164
SureCross™ DX80 M-GAGE™ Node with Integrated Battery
Modbus Register 13
Low Pass Filter
Sample High
Counter
Report
Rate
Sample Rate
Baseline
Filter
Threshold and
Hysteresis
Device Settings
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Filter Off
0
1
Filter Threshold 30, 2 Hour
1
0
Filter Threshold 30, 8 Hour
1
1
Threshold
Hysteresis
No Change
0
0
0
50
15
0
0
1
100
30
0
1
0
150
30
0
1
1
200
30
1
0
0
300
40
1
0
1
500
50
1
1
0
800
60
1
1
1
Sending the Configuration Message to Register 13
Modbus command 06 (write single holding register) is used in this example to set the parameter values for the M-GAGE Node. A sample
configuration message for Node 1:
Modbus Register 13
Low Pass Filter
Sample High
Counter
Report
Rate
Sample Rate
Baseline
Filter
Threshold and
Hysteresis
Bits
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Values
0
0
0
0
1
0
1
1
0
1
0
0
1
1
0
1
Hex Values
0
B
4
D
Sending this configuration message to register 13 sets the low pass filter to “no change;” the sample high counter to 2; the report rate and
sample rate to 125 milliseconds; the baseline filter to 0, 15; the threshold to 300; and the hysteresis to 40.
The complete Modbus command, in hexidecimal, is:
Slave ID#
Modbus
Command
Register Number
Configuration Value
01
06
00
1C
0B
4D
CRC
CRC
Configuration Using Registers 7, 15, and 16
To send Modbus configuration commands to registers 7, 15, and 16, please refer to the Modbus Host Configuration Reference Guide, Banner
document number 132114 for instructions and example commands.