Wiring diagrams for discrete inputs, Wiring diagrams for discrete outputs, Ip67 housing ip20 housing – Banner SureCross DX80 Wireless Networks User Manual
Page 5
IP67 Housing
IP20 Housing
A4+
A2-
A2+
GND
PWR
DO2
DI2
A3+
A1-
A1+
GND
PWR
DO1
DI1
A4- A3-
DI1
DI2
A1+
A1-
A2+
A2-
V-
V-
V+
B+
A4-
A4+
DO1
DO2
A3+
A3-
Tx
Rx
Ax+ and Ax-. Analog IN x. Analog inputs for devices requiring
more than one connection, such as thermocouples or RTDs.
When there is no Ax-, use Ax+ as an analog input.
DIx. Discrete IN x.
DOx. Discrete OUT x.
GND. Ground/dc common connection.
PWR. Power, 10 to 30V dc power connection.
B+. 3.6 to 5.5V dc (for battery powered models only).
RX/-. Serial comms line
TX/+. Serial comms line
V+. Power, 10 to 30V dc power connection.
V-. Ground/dc common connection.
Wiring Diagrams for Discrete Inputs
Connecting dc power to the communication pins will cause permanent damage. For the DX8x...C models, PWR in the wiring diagram
refers to V+ on the wiring board and GND in the wiring diagram refers to V- on the wiring board.
Discrete Input Wiring for PNP Sensors
Discrete Input Wiring for NPN Sensors
DIx
PWR
10-30V dc
DIx
GND
dc common
Wiring Diagrams for Discrete Outputs
Connecting dc power to the communication pins will cause permanent damage. For the DX8x...C models, PWR in the wiring diagram
refers to V+ on the wiring board and GND in the wiring diagram refers to V- on the wiring board.
Discrete Output Wiring (NPN or NMOS)
DOx
GND
PWR
10-30V dc
Load
dc common
SureCross DX80 FlexPower Thermocouple Node
P/N 131297 Rev. I
www.bannerengineering.com - tel: 763-544-3164
5