Wire sizing based on insulation rating – Calculated Industries 5060 User Manual
Page 40

38 — ElectriCalc Pro
Wire Sizing Based
on Insulation Rating
Wiring is being installed in a 240 volt,
single-phase system rated at 30 kVA.
What is the wire size needed if you use
60°C copper wire?
Steps
Keystrokes
Display
Clear calculator
o o
0.
Set to 1-phase
S 1
1 PH
Enter kVA
30 K V KVA 30.
Enter volts
240 U
VOLT 240.
Find amps
A
AMPS 125.
Find wire size
w AWG 0 CU
WIRE SIZE
Display Wire
Ampacity
w
0
125.0 Cu WIRE A
Display NEC Table
w
NEC 310.16
Set to 3 Phase
S 3
3 PH