User’s Guide — 13

Second Press
If a wire length has been entered, the
second press displays the smaller of
the two wire sizes. If not solving for
voltage drop wire size, then displays
the maximum ampacity.

Third Press
If a wire length has been entered, dis-
plays the minimum wire ampacity rat-
ing.

S w — 125% Ampacity
Used for motor wire sizing when the
wire must not exceed 80% of its rated
ampacity (125%A). This keystroke
calculates wire size based on 125% of
the entered or calculated amps value.
Displays: 125%.

P — Parallel Size
Used to find the size of parallel conduc-
tors using amperage and an entered
quantity of wires. Parallel wire size
calculations smaller than 1/0 are dis-
played as “none” (display shows
nonE”) as the NEC does not allow
parallel wire runs smaller than 1/0.

First Press
When preceded by a number, calcu-
lates the applicable wire size for that
quantity of wires in parallel.
Displays: PAR WIRE SIZE.