ELECTRICAL DATA - 1140 RPM MODELS 60Hz

M.C.A. = Minimum Circuit Ampacity (AMPS)
M.O.P. = Maximum Overcurrent Protection (AMPS)

ELECTRICAL DATA - 1140 (950) RPM MODELS 50Hz

M.C.A. = Minimum Circuit Ampacity (AMPS)
M.O.P. = Maximum Overcurrent Protection (AMPS)

NO.

OF

FANS

208-230/3/60

460/3/60

575/3/60

TOTAL

FLA

MCA

MOP

TOTAL

FLA

MCA

MOP

TOTAL

FLA

MCA

MOP

1

6.6

8.3

15

3.1

3.9

15

2.5

3.1

15

2

13.2

14.9

20

6.2

7

15

5

5.6

15

3

19.8

21.5

25

9.3

10.1

15

7.5

8.1

15

4

26.4

31

35

12.4

13.2

15

10

10.6

15

5

33

34.7

40

15.5

16.3

20

12.5

13.1

15

6

39.6

46

50

18.6

21

25

15

15.6

20

8

52.8

61

70

24.8

25.6

30

20

20.6

25

10

66

71

80

31

36

40

25

25.6

30

12

79.2

91

100

37.2

41

45

30

36

40

NO.

OF

FANS

200-220/3/50

380-400/3/50

TOTAL

FLA

MCA

MOP

TOTAL

FLA

MCA

MOP

1

5.9

7.4

15

2.7

3.4

15

2

11.8

13.3

15

5.4

6

15

3

17.7

19.1

25

8.0

8.7

15

4

23.6

25

30

10.7

11.4

15

5

29.5

36

40

13.4

16

20

6

35.3

41

45

16.1

16.8

20

8

47.1

51

60

21.4

26

30

10

58.9

71

80

26.8

31

35

12

70.7

81

90

32.2

36

40