Bally Refrigerated Boxes SmartVap Electronically Controlled System User Manual
Smartvap, Electronically controlled system, National refrigeration
SmartVap
TM
Electronically
Controlled System
Model: (Part # 1090200)
Electrical Power: 115/1/60, 208-230/1/60
1079817
PROGRAM SPECIFICATIONS
AND OPERATING
INSTRUCTIONS
Factory Settings:
This Defrost/Temperature control has been
COMPLETELY pre-set at the factory for Electric
Defrost mode. Room temperature default
factory setting is –10ºF. Simply re-adjust if
different room temperature setting is required.
If desired, clock can be set to display the
current time (24 hour mode)
.
It is recommended
to retain all other factory settings initially, and
re-adjust accordingly later, if required.
Also refer to control wiring diagrams on
following pages.
Note: After power - up, allow 15 seconds for
display to activate
“Time” Button Functions
To view TIME settings (in sequence listed below),
push and release the “Time” button
To adjust settings, hold down the “Time” button
while pushing “Up” or “Down” buttons.
Electronic Room Thermostat & Defrost Control
Electric Defrost Mode Program
Default DISPLAY shows actual room (zone)
temperature:
Display
Adjustment
Factory
Function
Shows:
Range:
Default
Setting:
24 hour time
“24:00”
00:00 to
NA
of day
24:00
Number of
defrosts per
“nd / 04”
nd01 to 12
nd / 04
day (24 hrs)
First defrost
“def 01 /
00:00 to
09:00
start time
09:00”
24:00
Maximum
“defd / 35”
1 min. to
35 min.
defrost duration
2 hours
NATIONAL
REFRIGERATION
Note: To gain access to control buttons, pry
up cover (use slot at bottom of cover)
Display shows:
Range:
“-10ºF”
-45ºF to 99ºF