Electrical data – Bally Refrigerated Boxes BVC Generation C – Direct Drive Air-Cooled – Vertical Air User Manual
Page 15

- 15 -
ELECTRICAL DATA - 550 RPM MODELS 60Hz
M.C.A. = Minimum Circuit Ampacity (AMPS)
M.O.P. = Maximum Overcurrent Protection (AMPS)
ELECTRICAL DATA - 550 (450) RPM MODELS 50Hz
M.C.A. = Minimum Circuit Ampacity (AMPS)
M.O.P. = Maximum Overcurrent Protection (AMPS)
NO.
OF
FANS
208-230/3/60
460/3/60
575/3/60
TOTAL
FLA
MCA
MOP
TOTAL
FLA
MCA
MOP
TOTAL
FLA
MCA
MOP
1
2.8
3.5
15
1.3
1.6
15
1.1
1.4
15
2
5.6
6.3
15
2.6
2.9
15
2.2
2.5
15
3
8.4
9.1
15
3.9
4.2
15
3.3
3.6
15
4
11.2
11.9
15
5.2
5.5
15
4.4
4.7
15
5
14.0
16
20
6.5
6.8
15
5.5
5.8
15
6
16.8
21
25
7.8
8.1
15
6.6
6.9
15
8
22.4
26
30
10.4
10.7
15
8.8
9.1
15
10
28.0
31
35
13
16
20
11
11.3
15
12
33.6
41
45
15.6
15.9
20
13.2
16
20
NO.
OF
FANS
200-220/3/50
380-400/3/50
TOTAL
FLA
MCA
MOP
TOTAL
FLA
MCA
MOP
1
2.2
2.7
15
1
1.2
15
2
4.4
4.9
15
2
2.2
15
3
6.5
7.1
15
2.9
3.2
15
4
8.7
9.3
15
3.9
4.2
15
5
10.9
11.4
15
4.9
5.1
15
6
13.1
16
20
5.9
6.1
15
8
17.4
21
25
7.8
8.1
15
10
17.4
21
25
7.8
8.1
15
12
26.2
31
35
11.8
12
15