Step: 4 install the new fan capacitor and bracket – Rockwell Automation 20D PowerFlex 700H/700S AC Drives Frame 10 & 12 Main Fan Capacitor Replacement Kit User Manual
Page 11

Rockwell Automation Publication PFLEX-IN025B-EN-P - September 2011
11
PowerFlex 700H and 700S AC Drives Frame 10 and 12 Main Fan Capacitor Replacement Kit
Step: 4 Install the New
Fan Capacitor and Bracket
1. Secure the new fan capacitor adapter bracket to the fan inverter assembly
using the new M8 x 16 mm hexagonal socket screw and washer provided in
the kit. Tightening torque is 12 N
•
m (106 lb
•
in).
2. Secure the new fan capacitor to the new fan capacitor bracket using the
M12 nut and lock washer provided in the kit. Tightening torque is 5 N
•
m
(44 lb
•
in).
IMPORTANT
Assemble the adapter bracket using the appropriate mounting
hole as shown in the illustration below.
New adapter
bracket
➀
Use this hole when
installing the adapter bracket
on the right-hand side fan
inverter assembly.
➁
Use this hole when
installing the adapter bracket
on the left-hand side fan
inverter assembly.
Nut
Washer
Bracket
Capacitor