PowerFlex® 700S and 700H Frame 13 Replacement Power Structures
Pre-Charge Connections on Drives with DC Input
You must connect the ASIC board connectors X9 and X15 to the X50
terminal block for the pre-charge circuit. The X50 terminal block is located
on the Control Frame in the left-hand enclosure. Refer to
for the location of these connection points. Refer to publication
PFLEX-IN006
…
, Installation Instructions - PowerFlex 700S and 700H
Frame 9-14 Drives, for more information regarding the pre-charge circuit.
X50 Terminal Block Connections
Figure 7 Sample Pre-charge Wiring Diagram
ASIC Board Charge Relay Contact Ratings
ASIC Board
Connector
Terminal
to
X50 Terminal Pre-Charge Circuit Connection Description
X9
25
. . .
1
Pre-charge Complete Signal (+24V DC)
26
. . .
2
Pre-charge Complete Signal (Common)
X15
21
. . .
3
Charge Relay Contact
23
. . .
4
Charge Relay Contact
M
F2
R2 CR2
DC+
DC Source
DC-
CR2
R1
F1
M
ASIC
Board
X9
X15
Precharge
Complete
25
26
21
22
23
CR1
M
CR2
M
CR1
2
X50
1
M
4
3
Charge
Relay*
* Refer to the “ASIC
Board Charge Relay
Contact Ratings” table
below.
External precharge circuitry is shown as dashed lines.
Load
Resistance load (cos
φ
= 1)
Rated load
8 A at 250 VAC: 5 A at 30 VDC
Rated carry current
8 A
Max. switching voltage
250 VAC; 30 VDC, (400 VAC)
Max. switching current
AC 8 A; DC 5 A
Max. switching power
2,000 VA; 150 W
Failure rate (reference value)
5 VDC 10 mA (for gold plating 0.35 µ min.)