beautypg.com

Rack 4: thrshout, Rack 5: line_flt, Table 10 rack 4: thrsout descriptions – Rockwell Automation T8433 Trusted TMR Isolated 4-20 mA Analogue Input Module - 20 Channel User Manual

Page 21: Table 11 rack 5; line_flt, Trusted, Module t8433

background image

Trusted

TM

Module T8433

Issue 11 Apr 10

PD-T8433

21

3.2.4. Rack 4: THRSHOUT

This board allows the current thresholds for an analogue input channel to be read or written by the
application. The application can write new thresholds in the THRSHOUT board for a particular channel,
and it can read the current thresholds from the THRSHIN board, under control of a channel in the
THRSHOUT board.

Channel

Description

1

Write the threshold data for a particular
input channel on channels 3 to 11 to the
module. The data is written on a rising
edge 0 to 1.

2

Read the threshold data for a particular
channel from the module to the THRSHIN
board. The data is read on a rising edge 0
to 1.

3

Channel number to write/read threshold
data. Range 1 to 20.

4

States 2 > 1 falling threshold

5

States 1 > 2 rising threshold

6

States 3 > 2 falling threshold

7

States 2 > 3 rising threshold

8

States 4 > 3 falling threshold

9

States 3 > 4 rising threshold

10

States 5 > 4 falling threshold

11

States 4 > 5 rising threshold

Table 10 Rack 4: THRSOUT descriptions

3.2.5. Rack 5: LINE_FLT

Channel

Description

1

Field input channel 1 line fault

2

Field input channel 2 line fault

20

Field input channel 20 line fault

21

Field input channel 1 redundant line fault

40

Field input channel 20 redundant line fault

Table 11 Rack 5; LINE_FLT

The line fault input state is reported as true (logic ‘1’) for a line fault condition (open circuit,
indeterminate, or short circuit condition). The logic state is the majority voted value.