Table 7 rack 2: state output bit descriptions, Table 8 rack 2: state input bit descriptions, Trusted – Rockwell Automation T8448 Trusted TMR Zone Interface Module - 40 Channel User Manual
Page 24: Module t8448

Trusted
TM
Module T8448
Issue 14 Apr 10
PD-T8448
24
The least significant 3-bits indicate the operational state of the channel. When configured as an output,
the states have the following meaning.
Value
Description
7
Channel Fault
6
Field fault (e.g. field leakage to 0V or 24V)
5
Short circuit in field wiring or load
4
Output energised (ON)
3
Open circuit in field wiring or load
2
Output de-energised (OFF)
1
No field supply voltage
0
Unused
Table 7 Rack 2: STATE Output bit descriptions
When configured as an input channel, the states are allocated to voltage ranges. The usual definition
for a digital input is as follows.
Value
Description
7
Channel Fault
6
Over Range
5
Short circuit
4
Contact Closed
3
Contact Indeterminate
2
Contact Open
1
Open Circuit
0
Under Range
Table 8 Rack 2: STATE Input bit descriptions
Note that channels configured as inputs do not have a direct Boolean indication of the input status. The
Toolset application must be programmed to recognise states 2 and 4 above as open and closed
contact input respectively. All other states are treated as fault conditions; the input status determination
in these states is application specific.