Trusted
TM
Module T8448
Issue 14 Apr 10
PD-T8448
21
3.1. Module Configuration
There is no configuration required to the physical module. All configurable characteristics of the
module are performed using tools on the EWS and become part of the application or system.ini file
that is loaded into the TMR Processor. The TMR Processor automatically configures the module after
applications are downloaded and during Active/Standby changeover.
The IEC1131 TOOLSET provides the main interface to configure the Zone Interface module. Details
of the configuration tools and configuration sequence are provided in PD-8082B Trusted
TM
Toolset
Suite. There are three procedures necessary to configure the module. These are:
1. Define the necessary I/O variables for the field data and module status data using the
Dictionary Editor of the IEC1131 TOOLSET.
2. Create an I/O module definition in the I/O Connection Editor for each I/O module. The I/O
module definition defines physical information, e.g. Chassis and Slot location, and allows
variables to be connected to the I/O channels of the module.
3. Using the Trusted
TM
System Configuration Manager, define custom LED indicator modes,
per-channel default or fail-safe states, and other module settings.