beautypg.com

1 analog output – Rockwell Automation Liqui-Flo 1.5 AC Power Modules V1.2 User Manual

Page 46

background image

7-2

LiquiFlo 1.5 AC Power Modules, Hardware Reference Version 1.2

7.1

Analog Output

The single analog output channel can be configured using Analog Out Config (340)
and Analog Out1 Sel (342) to select any one of 13 analog outputs. Terminals 1 and 2
output 4 to 20 mA. Terminals 17 and 18 output -10 to +10 volts. See table 7.1

Analog Out1 Sel (342) can be assigned the following values:

Table 7.1 – Analog Output Connection (Terminals 1- 2 or 17-18)

Terminal #

Signal

Related Parameters

1

I1- (Current -)

Analog Out Config (340) =1

2

I1+ (Current +)

17

V1- (Voltage -)

Analog Out Config (340) = 0

18

V1+ (Voltage +)

0 = Output Freq

7 = DC Bus Volts

1 = Command Freq

8 = PI Reference

2 = Output Amps

9 = PI Feedback

3 = Torque Amps

10 = PI Error

4 = Flux Amps

11 = PI Output

5 = Output Power

12 = %Motor OL

6 = Output Volts

13 = %Drive OL