Sample ftldint.bat file – Rockwell Automation FactoryTalk Historian SE 3.0 Live Data Interface User Guide User Manual
Page 47

8
●
Startup Command File
●
●
●
●
●
41
Parameter
Description
/q
Default = no queuing.
When the /q parameter is present, Snapshots and exceptions are
queued before they are sent to the PI Server node. The maximum
queue size is close to 4000 bytes. The queue is flushed between
scans if it is not filled. For an interface collecting unsolicited data, the
queue is flushed four times a second if it is not filled.
/TSofPIorFT
The /TSofPIorFT parameter specifies which time stamp will be used to
determine when to send data to the Historian server:
/TSofPIorFT=0 means using server time stamp
/TSofPIorFT=1 means using FTLD server time stamp
Notes:
By default, there is no /TSofPIorFT parameter in the .bat
file. In this case, the Historian Server time stamp will be
used.
An unsolicited point will always use FTLD Server time
stamps.
/MultiCom
Use the /MultiCom parameter if you want the PI-UniInt executable to
select the Multithreaded Threading model
(COINIT_MULTITHREADED) for the call to CoInitializeEx(). Otherwise,
the PI-UniInt will use the Apartment Threaded model
(COINIT_APARTMENTTHREADED).
Sample FTLDInt.bat File
The following is a sample startup command file that comes with the
installation:
“FTLDInt.exe”1 /uiDll=FTLDIntCtl.dll
/FTDirectory=$Global / FTContext=/ /PS=FTLD /ID=1
/host=localhost:5450 /ec=2 /pisdk=0 / maxstoptime=120
/q /sio /perf=8 /f=1 /f=0.05 /f=0.1 /f=0.25 / f=0.5
/f=2 /f=5 /f=10 /f=60 /f=120