Technical Specifications
A-3
Output Power
•
Output Voltage: 575 VAC, maximum
•
Modulation: Sine Wave, Pulse Width Modulation (PWM)
•
Short Circuit Rating: 65 KA
•
Power Dissipation: 534A Unit: 7500 W
972A Unit: 15000 W
1457A Unit: 22500 W
•
Output Inductor: 7.5 µH per phase (972A and 1457A units only)
•
Rail I/O Current Load: Power supply constraints dictate that any combination of
analog and digital I/O rails may be used as long as current
consumption does not exceed 1.5 A.
Output Current Ratings at 40° C (104° F) with 2 KHz Carrier Frequency:
Power Module
Part Number
Power Module
Description
Output Current
Rating
1
1. Derate Power Module output current by 5% for 50 Hz blower motor operation.
850020-11xxx, -21xxx
One Bay Cabinet
534 A
850020-12xxx, -22xxx
Two Bay Cabinet
972 A
850020-13xxx, -23xxx
Three Bay Cabinet
1457 A
Output Current Ratings
1
Based on Carrier Frequencies at 575 VAC Output
1. Derate Power Module output current by 5% for 50 Hz blower motor operation.
Power Module
Part Number
Carrier Frequency
2 KHz
4 KHz
2
2. The current limit is the continuous, maximum current rating and is duty cycle-dependent. The drive can be
operated at the overload (maximum) current for up to five minutes with a 10% duty cycle.
850020-11xxx, -21xxx
534 A
445 A / 534 A
850020-12xxx, -22xxx
972 A
890 A / 972 A
850020-13xxx, -23xxx
1457 A
1335 A / 1457 A
Typical Power Module Current
1
and Motor Ratings
Part
Number
230V Motor
380V Motor
460V Motor
575V Motor
Amps
KW
HP
Amps
KW
HP
Amps
KW
HP
Amps
KW
HP
850020-11xxx
850020-21xxx
534
168
225
534
277
371
534
336
451
534
419
561
850020-12xxx
850020-22xxx
972
305
409
972
505
677
972
611
819
972
765
1025
850020-13xxx
850020-23xxx
1457
459
615
1457
757
1015
1457
918
1230
1457
1146
1536
1. 100% rated output current ratings at 40° C (104° F) ambient air temperature at 2 KHz. Reduce all output current ratings by 5% when the