Trusted – Rockwell Automation T80015 Application Note Trusted SC300E Migration Process User Manual
Page 12

Trusted
TM
AN-T80015
Issue 01 Apr 08
AN-T80015
Page 12 of 16
Clicking on a SC300E chassis in the Trusted
TM
System Configuration tool and selecting
‘Jumper Config’ will display the required jumper settings for that chassis.
The link settings on the Triguard BIC chassis refer to the ‘Triguard Chassis Number’ not the
‘Logical Chassis Number’ which is the overall position of the chassis in the Trusted
TM
system.
The Controller rear view shows all connections
available via the Interface Adapters.
The Processor Interface Adapter provides
connection for system alarms and Modbus RTU
ports on the TMR Processor, as well as
enabling features such as Modbus master and
IRIG-B time synchronisation.
The Expander Interface Adapter has four or
seven connections available to individual
Trusted
TM
Expanders or the SC300E Main
Chassis using the Trusted
TM
SC300E Interface
Cable Assembly TC-322-02.
Other serial and Ethernet communications
capability is accessed through the
Communications Interface Adapters. Ethernet
RJ45 connection is specifically required for Peer
to Peer and OPC.
Due to the low current requirements of the 5Vdc supply to the 8161 Bridge modules it may be
necessary to fit a MXD dummy load module in the chassis, if no I/O modules are installed.
This is to provide a minimum load for the chassis 5Vdc power supplies.
Comms interface
adapter - DCS, peer
to peer & EWS
Expander
interface
adapter
Processor interface
adapter
(IRIG-b, MODBUS)
Connections to bus
adapter and Plantguard
Expanders
Interface cable
Comms interface
adapter - DCS, peer
to peer & EWS
Expander
interface
adapter
Processor interface
adapter
(IRIG-b, MODBUS)
Connections to bus
adapter and Plantguard
Expanders
Interface cable
Connections to bus
adapter and
Trusted
TM
Expanders