MINPAK PLUS

STANDARD BLANK

FACEPLATE

Figure 2 - Three Phase MinPak Plus With

Standard Blank Faceplate

CHASSIS

GROUND

WIRE

Figure 3 - Three Phase MinPak Plus With

Chassis Ground Wire Mounted to

Local Operators Control Cabinet Door Faceplate

AREA TO

BE CLEANED

WITH ALCOHOL

CIRCUIT

BREAKER

BOOT

Figure 4 - Local Faceplate With All Options

6. Pass the2 wireharnesses through theCover cutĆ

out, align the threaded studs with the holes, and

press the Faceplate into place. Check for an even

seating on the gasket.

7. Attach and tighten all 8 hex nuts until the Faceplate

bottoms out on thestops built into theCover. Use

an alternating pattern when tightening, but tighten

all nuts evenly. Attach the ground (green) wire to the

Faceplate with the standard nut provided. (Refer to

Figure3).

DANGER

IT IS NECESSARY TO ATTACH THE FACTORY

CHASSIS GROUND WIRE TO THE CONTROLĆ

LER CABINET DOOR VIA THE LOCAL OPERAĆ

TOR STATION FACEPLATE, PERSONAL INJUĆ

RY MAY RESULT IF THIS PRACTICE IS NOT

FOLLOWED.

CAUTION: CIf theOperator's Control Station FaceĆ

plate is not properly seated and firmly tightened,

theNEMA Type12 rating of thecontroller cannot be

maintained. Makesurethereis a firm seating

against thegasket.

8. Locatethearea on theRegulator Modulewherethe

2 connectors will connect. (Refer to Figure 6 and

Figure7). Notethereare2 sets of pins. Matethe

connector with thered wirein theend position conĆ

necting to the pin marked 32 (RED).