3 power module faults and warnings – Rockwell Automation SB3000 High Pwr SB3000 AC Pwr Modules (RCS) User Manual
Page 38
4-4
SB3000 Power Modules (RCS)
4.3
Power Module Faults and Warnings
The PMI Processor continually runs diagnostics which check for errors that may affect
system operation. Warnings are errors which indicate that the SB3000 Synchronous
Rectifier is not operating in an optimum manner. Warnings will not shut down the
SB3000. Faults are severe errors which will shut down the SB3000. See tables 4.3
and 4.4.
Refer to the SB3000 Synchronous Rectifier Configuration and Programming
instruction manual (S-3034) for more information about the Fault and Warning
registers.
Table 4.1 – DC Bus and Output Terminal Tests
1
1. With the AC input lines disconnected
Meter Connections
+ -
Scale
Expected Test Results
DC Bus
- Bus (45)
+ Bus (47)
X10
Capacitor Effect (0 to 50 ohms)
+ Bus (47)
- Bus (45)
Capacitor Effect (0 to 200 ohms)
Bus
Capacitors
+
1249
X10
Capacitor Effect (0 to 500 ohms)
-
1249
601
+
X1
2 ohms
602
+
603
+
+
601
X10
Capacitor Effect (0 to 2k ohms)
+
602
+
603
Input
Terminals
181 (601)
182 (602)
X1000
4k to 6k ohms
181 (601)
183 (603)
182 (602)
183 (603
Table 4.2 – IGBT Tests
1
1. With the AC input lines disconnected
Meter
Connections
+ -
Scale
Expected Test
Results
(+/- 10%)
W Phase (lower) +
183
+1147
2k
Ω
/diode
0.300 ohms
V Phase (lower) +
182
+1147
2k
Ω
/diode
0.300 ohms
U Phase (lower) +
181
+ 1147
2k
Ω
/diode
0.300 ohms
W Phase (upper) -
1245 -
183
2k
Ω
/diode
0.300 ohms
V Phase (upper) -
1245 -
182
2k
Ω
/diode
0.300 ohms
U Phase (upper) -
1245 -
181
2k
Ω
/diode
0.300 ohms