beautypg.com

Rockwell Automation 36С47 DC Drive Output Contactor Kit 300-500HP User Manual

Page 5

background image

21. Replace the outlet air duct over the nine loosened hex

head cap screws making sure all wiring is clear of the

duct. Tighten the screws.

22. Using the hardware supplied with the Contactor,

reconnect motor leads T1, T2 and T3 to terminals 1T1,

1T2, and 1T3, respectively, on the load side of the

Contactor.

23. Using the two supplied spacers, the two 1/4Ć20 x 1

1/4" hex head cap screws, and the two remaining 1/4"

flat washers and 1/4" lock washers; install the Cover

(705321Ć15R) on the Contactor.

24. ReĆapply power the AĆC VLS Drive.

Figure 6. Connecting Wire Harnesses 801553Ć34R and Ć35R.

CONTACTOR

CONTROL

TRANSFORMER

FUSE

RELAY

TB1

REGULATOR

WIRE HARNESS

801553Ć34R

AUXILIARY

CONTACT

WIRE HARNESS

801553Ć35R