connect the other end to the hole preĆdrilled in the
back panel below the Control Transformer. See
Figures 2, 5 and 7.
16. Connect Wire Assembly 608809Ć12RX (labeled 288)
between the Fuse and the Control Transformer. See
figures 2, 5 and 7.
17. Connect Wire Assembly 608809Ć12SC between
terminals 1 and 3 on the Contactor terminal board.
See Figure 5.
18. Referring to Figures 6 and 7 and Table 2, connect Wire
Harness 801553Ć34R beginning in the left bay of the
controller. Route the harness thru the back channel
located above the power module, thru the bottom
opening at the top of the side wall, thru the back
vertical channel to the respective connection points.
Note that leads 11 and 289 will route thru the back
channel located above the Control Transformer.
Harness Lead
Numbers
(both ends)
From
To
388
ă11
381
383
289
Fuse
Relay
Control Transformer H
1
Control Transformer H
4
Control Transformer X
2
Relay
L1 on Contactor
Transformer Line Fuse
Transformer Line Fuse
L2 on Contactor
19. Referring to Figures 6 and 7, connect Wire Harness
801553Ć35R to the Auxiliary Contact installed in Step
3. Route the harness in the front channel (outermost)
located above the Control Transformer, up the front
vertical channel, thru the top opening at the top of the
side wall, thru the front channel located above the
power module, down the front vertical channel, thru
the horizontal channel located above the regulator, to
terminals 43 and 53 on TB1 of the regulator.
20. Support the wire harnesses and assemblies as
necessary with the furnished tyĆraps.
Figure 5. Connecting Wire Assemblies 608809Ć12X, Ć12RX and Ć12SC.
WIRE ASSEMBLY
608809Ć12RX
WIRE ASSEMBLY
608809Ć12SC
CONTACTOR
CONTROL
TRANSFORMER
FUSE
WIRE ASSEMBLY
608809Ć12X