Rockwell Automation T8480 Trusted TMR Analogue Output Module - 40 Channel User Manual
Tmr analogue output module – 40 channel, Introduction, Trusted
Trusted
TM
PD-T8480
Issue 13 Apr 10
PD-T8480
1
Trusted
TM
TMR Analogue Output
Module – 40 Channel
Introduction
The Trusted
TM
TMR Analogue Output module interfaces to 40 field devices. Triplicated diagnostic
tests are performed throughout the module including measurements for current, and voltage on each
portion of the voted output channel. Tests are also performed for stuck on and stuck off failures. Fault
tolerance is achieved through a Triple Modular Redundant (TMR) architecture within the module for
each of the 40 output channels.
Automatic line-monitoring of the field device is provided. This feature enables the module to detect
both open and short circuit failures in field wiring and load devices.
The module provides on-board Sequence of Events (SOE) reporting with a resolution of 1ms. An
output change of state triggers an SOE entry. Output states are automatically determined by voltage
and current measurements on board the module.
Features
• 40 Triple Modular Redundant (TMR) output channels per module.
• Comprehensive, automatic diagnostics and self-test.
• Automatic line monitoring per point to detect open circuit and short circuit field wiring and
load faults.
• 2500V dc optical isolation barrier.
• On-board Sequence of Events (SOE) reporting with 1ms resolution. Module can be hot-
replaced on-line using dedicated Companion (adjacent) Slot or SmartSlot (one spare slot for
many modules) configurations.
• Front panel output status LEDs for each point indicate output status and field wiring faults
• Front panel module status LEDs indicate module health and operational mode (Active,
Standby, Educated)
• T
5
V Certified for non-interfering applications
• Outputs are powered in isolated groups of eight
Document Outline
- 1. Description
- 2. Installation
- 3. Application
- 4. Operation
- 5. Fault Finding and Maintenance
- 6. Specifications