The Common Memory Module Is In Any

Even Slot Other Than 0

In the following, assume the Common Memory module is in slot 2 and the single

Processor module in the rack is in slot 1. Recall that in this configuration, common

variables, as well as local variables, are being stored on the Processor module.

Status of Data

Common

Action

App.

Task

Deleted?

App.

Task

Status

NonVol

Vol

I/O

Local

Replace 57C413A with

Same or new 57C413A

ąAt power up

NO

STOP

Data OK

Zero

Lost

(Random)

Data OK

Replace 57C413A with

New 57C413B or

57C423

ąAt power up

NO

STOP

Data OK

Zero

Zero*

Data OK

Replace 57C413A with

programmed 57C413B

or 57C423 (module may

contain data from

another application)

ąAt power up

NO

STOP

Data OK

Zero

Value from

programmed

module at

same

address*

Data OK

Replace 57C413B or

57C423 with New

57C413B or 57C423

ąAt power up

NO

STOP

Data OK

Zero

Zero*

Data OK

Replace 57C413B or

57C423 with proĆ

grammed 57C413B or

57C423 (module may

contain data from

another application)

ąAt power up

Error Code 13 appears on Processor LEDs**

Replace battery on

57C413B or 57C423 and

return same module to

rack

ąAt power ***

NO

STOP

Data OK

Zero

Data OK

Data OK

* To ensure your application task does not access old or incorrect data, create

a BASIC task to write zeroes to each register location before you run any

other application tasks.

** Select DOWNLOAD from the ON LINE menu to download the configuration

and application tasks. Select ERROR CLEAR to clear the LED fault code on

the Processor module. Refer to JĆ3630 for more information about the ON

LINE menu.

*** Assumes superĆcapacitor has maintained memory on the module during the

time required to replace the battery.