Appendix e, Continued) – Rockwell Automation 57C423 Common Memory Module User Manual
Page 36
EĆ2
Appendix E
(Continued)
The Common Memory Module Is In Any
Even Slot Other Than 0
In the following, assume the Common Memory module is in slot 2 and the single
Processor module in the rack is in slot 1. Recall that in this configuration, common
variables, as well as local variables, are being stored on the Processor module.
Status of Data
Common
Action
App.
Task
Deleted?
App.
Task
Status
NonVol
Vol
I/O
Local
Replace 57C413A with
Same or new 57C413A
ąAt power up
NO
STOP
Data OK
Zero
Lost
(Random)
Data OK
Replace 57C413A with
New 57C413B or
57C423
ąAt power up
NO
STOP
Data OK
Zero
Zero*
Data OK
Replace 57C413A with
programmed 57C413B
or 57C423 (module may
contain data from
another application)
ąAt power up
NO
STOP
Data OK
Zero
Value from
programmed
module at
same
address*
Data OK
Replace 57C413B or
57C423 with New
57C413B or 57C423
ąAt power up
NO
STOP
Data OK
Zero
Zero*
Data OK
Replace 57C413B or
57C423 with proĆ
grammed 57C413B or
57C423 (module may
contain data from
another application)
ąAt power up
Error Code 13 appears on Processor LEDs**
Replace battery on
57C413B or 57C423 and
return same module to
rack
ąAt power ***
NO
STOP
Data OK
Zero
Data OK
Data OK
* To ensure your application task does not access old or incorrect data, create
a BASIC task to write zeroes to each register location before you run any
other application tasks.
** Select DOWNLOAD from the ON LINE menu to download the configuration
and application tasks. Select ERROR CLEAR to clear the LED fault code on
the Processor module. Refer to JĆ3630 for more information about the ON
LINE menu.
*** Assumes superĆcapacitor has maintained memory on the module during the
time required to replace the battery.