beautypg.com

Rockwell Automation 57C423 Common Memory Module User Manual

Page 23

background image

5Ć3

program. Verify that any IOREAD functions and IOWRITE

statements are using valid addresses.
If IOREAD functions and IOWRITE statements are using

valid addresses or if the error message in question was

51" through 58", use the I/O MONITOR function to

display the registers on the memory module. Remember

to specify the correct logical slot.
If you can monitor the inputs, the problem lies in the

application software (proceed to step 3). If you cannot

monitor the inputs, the problem lies in the hardware

(proceed to step 4).

Step 3.

Verify that the variable names are consistent with what is

used in the application task.
If you are using the AutoMax Programming Executive

Version 2.1 or earlier, verify that the variables defined by

IODEF and MEMDEF statements in the configuration task

match the variable names used in the application task.
In AutoMax Version 3.0 or later, verify the information on

the Variable Configurator form" (screen)is consistent with

the variable names used in the application task.

Step 4.

Verify that the hardware is working correctly.
Systematically swap out the Common Memory module,

the Processor module(s)and the backplane. Make certain

power is off before removing any module from the rack.

After each swap, if the problem has not been corrected,

replace the original item before swapping out the next

item.

This manual is related to the following products: