beautypg.com

2 module replacement – Rockwell Automation 57C423 Common Memory Module User Manual

Page 14

background image

3Ć2

P/S

0

1

2

3

4

5

6

7

8

9 10 11 12 13 14 15

10

Typical 10 Slot Rack

16

Typical 16 Slot Rack

Figure 3.1Ć Rack Slot Numbers

Step 5.

Turn on power to the rack.

Step 6.

Verify the installation. If the Common Memory module was

placed in slot 0, the powerĆup diagnostics performed

automatically by a Processor module should verify that the

module is operational.
If the Common Memory module is placed in any even slot

other than 0, it must be manually tested like a standard I/O

module. Connect the personal computer to the system

and run the Programming Executive Software.
Stop all programs that may be running.
Use the I/O MONITOR function and enter the module slot

number and any valid register number (0Ć32767). Also

enter the slot number +1 and any valid register number

(0Ć32767)to test the upper 32K register of memory. Verify

that data can be read from and written to the registers. To

ensure your application task does not access old or

incorrect data, you may want to create a BASIC task to

write zeroes to each register location before you run any

other application tasks. This is only required if you do not

initialize values in your application tasks.

3.2

Module Replacement

Removing or replacing the Common Memory module may affect

tasks and variables in the rack. Before beginning the procedure

below, refer to Appendix E for DCS 5000 racks or Appendix F for

AutoMax racks.
Use the following procedure to replace a module:
Step 1.

Stop any application tasks that may be running.

Step 2.

Turn off power to the rack and all connections.

Step 3.

Use a screwdriver to loosen the screws that hold the

module in the rack. Remove the module from the slot in

the rack.

Step 4.

Place the module in the antiĆstatic bag it came in, being

careful not to touch the connectors on the back of the

This manual is related to the following products: