beautypg.com

Parts list, Install the micro800 remote lcd – Rockwell Automation 2080-REMLCD Micro800 Remote LCD Installation Instructions User Manual

Page 9

background image

Micro800 Remote LCD 9

Rockwell Automation Publication 2080-IN010A-EN-P – December 2013

Parts List

The Micro800 Remote LCD module ships with these items:

Allen-Bradley sticker label

Clamp accessories for panel mounting (4 pcs)

Product Information (publication 2080-PC002)

Install the Micro800 Remote LCD

Before installing the Remote LCD through the front panel, review minimum clearances, panel
guidelines, panel cutout dimensions, and product dimensions.

Minimum Spacing

Maintain spacing from objects such as enclosure walls, wireways, and adjacent equipment. Allow
50.8 mm (2.0 in.) of space on all sides for adequate ventilation. If optional accessories/modules
are attached such as the optional power supply, 2080-PS120-240VAC, make sure that there is
50.8 mm (2.0 in.) of space on all sides after attaching the optional parts.

Plan for adequate space around the module, inside the enclosure, for ventilation and cabling.
Consider heat produced by other devices in the enclosure. The ambient temperature around the
module must be -20…50 °C (-4…122 °F).

Panel Guidelines

Supporting panels must be at least 16 gauge to provide proper sealing against water and dust and
to provide proper support. The panel surface must be flat and free of imperfections to maintain
an adequate seal and NEMA/IP Type ratings.

IMPORTANT

Most applications require installation in an industrial enclosure to
reduce the effects of electrical interference and environmental
exposure. Locate your device as far as possible from power lines, load
lines, and other sources of electrical noise such as hard-contact
switches, relays, and AC motor drives. For more information on proper
grounding guidelines, see the Industrial Automation Wiring and
Grounding Guidelines, publication

1770-4.1

.

TIP

The minimum spacing requirements are sufficient for connecting cables and inserting.
Plan for additional clearance if using the USB host port on the back of the unit.