8. Feed the ground wire out the right side of the unit and through the

wireway cutout in the right hand unit support. Attach the unsecured end
of the wire to the front flange of the sidesheet with a 10-32
thread-forming screw. Use the small hole below the notch that is level
with the unit support pan (Figure 4). Torque the screw to 32 lb-in
(3.6 N-m).

9. Complete the unit insertion procedure.

NOTE: If large cables are being wired to unit devices, it may be necessary to
enlarge the wireway cutout in the right hand unit support for easier access and
increased bending room.

10. Mount the door to the structure and insert the hinge pins.