Rockwell Automation 2090-CPWM7DF-xxAFxx Continuous Flex Power Cables with DIN SpeedTec Connector Installation Instruc User Manual
Page 5
Continuous Flexible Power Cables Installation Instructions 5
Publication 2090-IN025A-EN-P — October 2009
Never bend a cable tighter than the specified bend radius. Refer to
for value.
3. When installing a continuous flexible cable observe these restrictions on the
flex zone and installation area:
• The flex zone is the area in which the cable can repeatedly flex up to its
specified bend radius.
• The installation areas require rigid mounting to prevent the cable from
flexing where it connects to other components.
4. Identify each connection on a cable by attaching a label around the outer
insulation of each wire adjacent to the drive connection.
5. Remove the O-ring on the motor connector when using a power cable with
a SpeedTec power plug.
The type of plug on the cable determines whether an O-ring is required on
the receptacle.
IMPORTANT
The O-ring dampens the effects of vibration at the cable-to-motor connection. This
creates a more secure connection for a cable with a threaded plug.
SpeedTec Plug
Threaded Plug
Remove O-ring when mating with a
SpeedTec plug.
Install O-ring when mating with a
threaded plug.
O-ring in groove.
If an O-ring is installed, a SpeedTec plug will not engage with the receptacle.