Connecting DC Power

The L1 and L3 versions (Catalog Number 2711-K5A1L1 or 2711-K5A1L3) of the
PV550 terminals connect to a 24V dc power source.

The table below shows the electrical ratings for the DC versions of the terminals.
Electronic circuitry and an internal fuse protect the terminals from reverse polarity
and over-voltage conditions.

Terminal Type

Supply Voltage

Power Consumption

PV550

18…30V DC, (24V DC nominal)

12 Watts maximum
(0.5 Amps @ 24V DC)

ATTENTION

Do not connect the PanelView terminal to an AC power source. Connecting to an
AC power source may damage the terminal.

The PanelView 550 terminal is designed for safe use when installed in a suitably
rated NEMA Type 12, 13, 4X (indoor use only), IP54 or IP65 enclosure.

L1

L2

White

(neutral)

Green (earth

ground)

L1

L2

Black (line)

Brown (line)

Green/Yellow

(protective earth)

Blue

(neutral)

120/240V AC, 3 Wire,

U.S. Color Code

120/240V AC, 3 Wire,

European Harmonized Color

Code

Power Terminal Block (fixed)

To Power Source

To Power Source

GND

GND