Rockwell Automation 2094-PRx Kinetix 6000 Power Rail Installation Instructions User Manual
Page 5
Kinetix 6000 Power Rail 5
Publication 2094-IN003D-EN-P - November 2010
Follow these steps to mount your 2094-PRS
x or 2094-PRx power rail.
1. Lay out the position for your power rail in the enclosure.
Refer to your servo drive user manual for panel layout recommendations. Mounting hole
dimensions for the power rail are shown in the figures on
2. Attach the power rail to the cabinet.
The recommended mounting hardware is M6 metric (1/4x20) bolts. Refer to the System
Design for Control of Electrical Noise Reference Manual, publicatio
,
for HF bonding techniques.
3. Tighten all mounting fasteners.
Apply 5.08 N•m (45.0 lb•in) torque.
4. Attach the braided grounding strap from the grounding stud to the bonded cabinet
ground.
IMPORTANT
To improve the bond between the power rail and subpanel, construct
your subpanel out of zinc plated (paint-free) steel.
LIM
PRS
PR
Bonded Cabinet Ground Bus
2094-PRSx or 2094-PRx Power Rail
(2094-PRS8 power rail is shown)
2094-PRSx or 2094-PRx Power Rail
on Bulletin 2094 Mounting Brackets
(2094-PRSx power rail is shown)
Ground Grid or Power
Distribution Ground
Braided Ground Strap, 100 mm (3.9 in.)
Braided Ground Strap, 100 mm (3.9 in.)
Ground Stud
Ground Stud
2094-XNBRKT-1 Mounting Bracket
Bonded Cabinet Ground Bus
Ground Grid or Power
Distribution Ground