Rockwell Automation 1799-D16U16BL 16 Input/16 Output Discrete Embedded I/O User Manual
Page 23
16 Input/16 Output Digital Embedded I/O Boards 23
Publication 1799-IN004F-EN-P - September 2008
Attribute
Value
EFT/B immunity
IEC 61000-4-4:
±2 kV at 5 kHz on power ports
±2 kV at 5 kHz on signal ports
±2 kV at 5 kHz on communication ports
Surge transient immunity
IEC 61000-4-5:
±500V line-line (DM) and ±1 kV line-earth (CM) on dc power ports
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
±2 kV line-earth (CM) on communication ports
Conducted RF immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80%AM from 150 kHz...80 MHz
Certifications
Certification (when
product is marked)
(1)
(1)
See the Product Certification link at
details.
Value
c-UR-us
UL Recognized Component Industrial Control Equipment, certified for US and
Canada. See UL File E65584.
CE
European Union 2004/108/EC EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick
Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
ODVA
ODVA conformance tested to DeviceNet specifications
Environmental