Auxiliary power specifications – Rockwell Automation 1799-D16U16BL 16 Input/16 Output Discrete Embedded I/O User Manual
Page 11
16 Input/16 Output Digital Embedded I/O Boards 11
Publication 1799-IN004F-EN-P - September 2008
The DeviceNet wire insulation colors are shown below.
Auxiliary Power Specifications
P1 1799-D16U16V and -D16U16VL I/O Connector
Pin
Signal
Pin
Signal
Pin
Signal
8
Common Return
25
Input 11
41
Input 10
9
Output 4
26
Input 9
42
Input 8
10
+24V dc-GRP 0
27
Input 14
43
Common In GRP 1
11
Output 5
28
Input 12
44
Input 13
12
Output 7
29
Output 6
45
Input 15
13
Output 0
30
Not Used
46
Not Used
14
Output 1
31
Not Used
47
Not Used
15
+24V dc-GRP 0
32
Not Used
48
Not Used
16
Output 2
33
Not Used
49
Not Used
17
Output 3
50
Not Used
P3 DeviceNet Connector
Pin
Insulation Colors
1
Black
2
Blue
3
Shield
4
White
5
Red
ATTENTION
To comply with the CE Low Voltage Directive (LVD), this equipment and all connected I/O
must be powered from a source compliant with the following:
•
Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).
To comply with UL restrictions, this equipment and all connected I/O must be powered
from a source compliant with the following:
•
10...30V dc Class 2 Power Supply or a 10...30V dc UL Listed or Recognized Power
Supply with isolated outputs limited to 200VA in each ungrounded output line. This
equipment and its power source must be mounted in a suitable enclosure with