beautypg.com

Ac line filter dimensions – Rockwell Automation 2198-DB42-F Kinetix 5500 AC Line Filters Installation Instructions User Manual

Page 5

background image

Kinetix 5500 AC Line Filters 5

Rockwell Automation Publication 2198-IN003A-EN-P - July 2012

Wiring Specifications

AC Line Filter Dimensions

AC Line Filter Dimensions (catalog number 2198-DB08-F)

Kinetix 5500
Drive Cat. No.

Line Filter
Cat. No.

Connects to

Terminals

Recommended

(1)

Wire Size
mm

2

, AWG

(1)

The actual gauge of the input power wiring depends on the system configuration. Consult your machine builder, the NEC, and applicable local
codes.

AC Line Filter
Strip Length
mm (in.)

Terminal
Torque Values
N•m (lb•in)

Pin

Signal

2198-H003-ERS

2198-DB08-F

(2)

(2)

Applies to installations with single-phase or three-phase input power.

IPD-1
IPD-2
IPD-3
IPD-4

1.5…4
(16…12)

7.5 (0.30)

0.8 (7.1)

2198-H008-ERS

2198-H015-ERS

2198-H025-ERS

2198-DB20-F

9.0 (0.35)

2.0 (17.7)

2198-H040-ERS

2198-H070-ERS

2198-DB42-F

1.5…6
(16…10)

12.0 (0.47)

L1
L2
L3

Ø 6.0
(0.24)

167

(6.57)

8.5
(0.33)

R3.0
(0.12)

32

(1.26)

173

(6.81)

151

(5.94)

1.2

(0.05)

179

(7.05)

60.8

(2.39)

46

(1.81)

79

(3.11)

M5

Dimensions are in mm (in.).