Wire the AC Line Filter
Wire should be copper with 75 °C (167 °F) minimum rating. Phasing of main AC power is
arbitrary and earth ground connection is required for safe and proper operation.
Wiring Examples for the AC Line Filter
IMPORTANT
The National Electrical Code and local electrical codes take precedence over the values and
methods provided.
IMPORTANT
When wiring the line filter for single-phase operation, do not make connections to the L3
terminals. Line and load designations must be observed to meet product specifications.
L1
L2
L3
L1
L2
L3
PE
L1’
L2’
L3’
PE
240/480V
L1
L2
L3
L1
L2
L3
PE
L1’
L2’
L3’
PE
240V
Bonded Cabinet
Ground Bar
2198-DB08-F
AC Line Filter
Input Fusing
Mains AC Input
Line
Load
Bonded Cabinet
Ground Bar
2198-DB
xx-F
AC Line Filter
Input Fusing
Mains AC Input
Kinetix 5500 drive input
power (IPD) connections
for three-phase operation.
Line
Load
Kinetix 5500 drive input
power (IPD) connections
for single-phase operation.