Before You Begin
For general guidelines when laying out your panel and mounting your AC line filter, refer to the
System Design for Control of Electrical Noise Reference Manual, publicatio
.
For guidelines specific to your application, refer to the Kinetix 5500 Servo Drives User Manual,
publication
Install the AC Line Filter
Mount the line filter to the cabinet panel with hardware as specified in the table below.
Refer to the System Design for Control of Electrical Noise Reference Manual, publication
performance.
ATTENTION: To avoid personal injury or damage to equipment due to hazardous voltages,
follow these guidelines when installing your AC line filter. NEC and local regulations always
take precedence.
•
Disconnect mains power prior to installation.
•
Verify that the rated voltage is compatible with the local supply voltage.
•
Connect the earth ground connection first when making connections.
Cat. No.
Mounting Bolts
Torque Value
N•m (lb•in)
2198-DB08-F
M5 (#10-32)
2.0 (17.7)
2198-DB20-F
2198-DB42-F
M6 (1/4x20)
4.5 (39.8)