beautypg.com

Disconnect power to the terminal, Remove the existing terminal from the panel, Attach the cutout adapter plate to the panel – Rockwell Automation 2711P-RAK12e Adapter Kit for PanelView 1200/1200E/1400E Keypad Terminal Cutout User Manual

Page 4

background image

4 Adapter Kit for PanelView 1200/1200e/1400e Keypad Terminal Cutout

Publication 2711P-IN015C-EN-P - March 2007

Disconnect Power to the Terminal

1. Disconnect power at the source and remove the power cord from the

PanelView 1200/1200e/1400e terminal.

2. Disconnect all communication cables from the PanelView terminal.

Remove the Existing Terminal from the Panel

1. Remove the mounting clips or nuts and washers that secure the PanelView

1200/1200e/1400e terminal to the panel.

2. Slide the terminal out from the panel.

Attach the Cutout Adapter Plate to the Panel

1. Align the studs on the cutout adapter plate with the existing stud holes on

the front of the panel.

2. Push the cutout adapter plate onto the panel until the gasket material is flush

with the front of the panel.

3. Using the 18 nuts with flat and lock washers, fasten the cutout adapter plate

onto the studs until the gasket is slightly compressed against the front of the
panel.

4. Using the torque wrench, tighten the nuts to not more than 10 lb-in to

maintain a NEMA Type 4X rating.

Do not over-tighten.

ATTENTION

Make sure that the power cord of the terminal is disconnected, and that all
cables have been disconnected from the rear of the terminal.