Rockwell Automation 2500 CENTERLINE MCC Joining and Splicing Columns User Manual
Page 11

Publication 2500-IN004A-EN-P - August 2009
CENTERLINE 2500 Motor Control Centers Installing, Joining and Splicing Columns 11
4. Slide the columns together making sure cabinets are level and
joining holes are aligned.
5. If lifting angles are removed from IP54 enclosures, you must seal
the lifting angle bolt holes with the caulking sealer.
6. For Front-only Configured Single Column Shipping Blocks,
remove the bottom horizontal wireway cover to fasten the front
of the MCC to the foundation.
If rear access is available, remove the back plate and fasten the
rear of the MCC to the foundation as illustrated in
Preferred
Mounting Arrangement
. If rear access is not available, fasten the
first column to the foundation before moving adjacent columns
into place.
Preferred Mounting Arrangement
7. For Front-only Configured Two Column Shipping Blocks,
remove the bottom horizontal wireway cover to fasten the front
of the MCC to the foundation.
700,0
(27.56)
642,0
(25.28)
561,0
(22.09)
69,0
(2.72)
29,0
(1.14)
82,0
(3.23)
18,0
(0.71)
600,0 - 800,0
(23.62 - 31.50)
44,0
(1.73)
513,0 - 713,0
(20.20 - 28.07)
438,0 - 638,0
(17.24 - 25.12)
234,0
(9.2)
6,0
(0.24)
Front-only Configured, Single Column
Shipping Blocks
Dimensions are in mm and (in.)
Diagram illustrates 600,0 and 800,0 mm
(23.62 and 31.50 in.) column depth
Protective Earth
Conductor
Front
(4) Mounting
Holes