Rockwell Automation 2711P Creating Modbus Applications User Manual
Page 45

Publication 2711P-UM002B-EN-P - March 2007
Installing KEPServer Drivers on Terminal 45
3. If other PanelView Plus terminals exist on the same Ethernet
network, the following error may display:
Error registering name on network (may be duplicate). Change
in system Control Panel and try again.
Ignore this error. It will be corrected during the upgrade. Press
OK to acknowledge error and wait for terminal to reset.
4. On touch or touch/screen terminals, you must calibrate the
touch screen by selecting pointers in all four corners of the
screen and pressing the middle of the screen when prompted.
5. Ignore the following message if it appears. It means RSView ME
is being installed. Do not touch the two buttons that appear
with this message.
Machine edition may be corrupted. Do you want to download
firmware?
6. When the upgrade is complete, a dialog appears requesting you
to remove the compact flash card from the card slot. Remove the
card and press F8 or Exit to reset the terminal.
7. Communication settings are cleared when the terminal is
upgraded. If Ethernet communications is used, reconfigure the
Ethernet communication settings using the values recorded
when preparing the terminal.
8. Replace the .MER files that you backed up before starting the
upgrade or download a new .MER file to the terminal.
9. Load the .MER file and run the project.
TIP
If a USB mouse is available you can acknowledge this
error by selecting OK.
TIP
Kepware drivers were installed on terminal. On
PanelView Plus CE terminals, you can go to the Storage
Card/KEPServer/Drivers folder to verify that the driver dll
exists.
TIP
You can configure your application to start automatically
on power cycle under Startup Options.