2 Low-profile Connector Kit for I/O and Cascading Safe Torque-off Signals

Rockwell Automation Publication 2090-IN043A-EN-P - December 2011

Install the Low-profile Connector Kit

Attribute

2090-K6CK-D44S0

Cascading cable connectors

M8 sockets (female) S0 output connector

M8 pins (male) S0 input connector

Screw terminal wire size

0.2…0.75 mm

2

(24…18 AWG)

Recommended wire strip length

5 mm (0.2 in.) single conductor

Recommended torque

Mounting screw
Terminal screws
Clamp and cover screws

0.4 N•m (3.5 lb•in)
0.2 N•m (2.1 lb•in)
0.4 N•m (3.5 lb•in)

ATTENTION: This connector kit contains electrostatic discharge (ESD) sensitive parts that can be
damaged if you do not follow ESD control procedures. If you are unfamiliar with ESD control
procedures, refer to Guarding Against Electrostatic Damage, publication

8000-4.5.2

, or any other

applicable ESD protection handbook.

P2

P1

P4

P3

P6

P5

P2

P1

P4

P3

P6

P5

40
42
39
39
41
40
0

40
44
39
39
43
40

14
25
17
26
18
15
0
0

27
28
19
20
23
24
21
22

27
28
19
20
23
24
21
22

14
25
17
26
18
15
0
0

40
42
39
39
41
40
0

40
44
39
39
43
40

S0
IN

S0

OUT

Follow these steps to form a compact
connection on I/O and safety wires.

1. Push the insulation down-and-over itself.
2. Move the insulation so it butts against the

outside wall of the cover.

3. Tape or shrink-wrap the end of the

insulation to the cable.

Mounting
Screws (3)

If necessary, turn clamps over
to hold small wires securely.

Shrink-wrapped Insulation

Use shield clamps (2) to maximize contact with

cable shield for high-frequency bonding.

Use tie wraps (2) for stress relief.

I/O

Cable/Wires

Cascading S0

Safe-off Cables

Safety

Cable/Wires