Install Latch Angle Bracket
The latch angle bracket installs in the top-right corner of the Feeder unit
compartment. Follow these steps to install the latch angle bracket.
1. Remove the plastic retaining clip from the right-hand unit support pan.
2. Secure the latch angle bracket to the right-hand unit support with a ¼-20
screw and lock washer and tighten to 55 lb•in (6 N•m) with a 3/8 in.
socket wrench.
TIP
The latch angle bracket has two tapped holes, but only one hole is used for
mounting. The tapped hole used depends on where the Feeder unit was
mounted in the section:
• If the Feeder unit was mounted directly below the top horizontal wireway
pan, then the bottom tapped hole of the latch angle bracket is used to
mount the bracket to the right-hand unit support.
• Otherwise, use the top tapped hole of the latch angle bracket.
Latch Angle
Bracket
¼-20 Screw and
Lock Washer
55 lb•in (6 N•m)
Latch Angle
Bracket
Mounting Holes