Feeder Circuit Breaker Units Secure Support Pan and Change Door Latch
2. Remove the plastic retaining clip from the unit support pan and secure the
unit support pan to the right-hand unit support with a 1/4-20 bolt, lock
washer, and nut.
3. Tighten to 55 lb•in (6 N•m) with a 3/8 in. socket wrench.
4. If the unit at the top of the section, directly above the Feeder unit, is a
Main Lug Compartment (Bulletin 2191) unit, a Main Disconnect Switch
(Bulletin 2192M) unit, or a Main Circuit Breaker (Bulletin 2193M) unit,
complete these steps:
a. Remove the plastic retaining clip.
b. Secure the top horizontal wireway pan to the right-hand unit support
with a 1/4-20 bolt, lock washer, and nut.
c. Tighten to 55 lb•in (6 N•m) with a 3/8 in. socket wrench.
5. If the unit at the bottom of the section, directly below the Feeder unit, is a
Main Lug Compartment (Bulletin 2191) unit, a Main Disconnect Switch
(Bulletin 2192M) unit, or a Main Circuit Breaker (Bulletin 2193M) unit,
complete these steps:
a. secure the bottom horizontal wireway pan to the right-hand unit
support with a 1/4-20 bolt, lock washer, and nut:
b. Tighten to 55 lb•in (6 N•m) with a 3/8 in. socket wrench.
Remove
Retaining Clip
Tighten to 55 lb•in
(6 N•m)
Top Horizontal
Wireway Pan
Tighten to 55 lb•in
(6 N•m)