Setting the data rate – Rockwell Automation 2705-DN42 DeviceNet Interface Communicaton Board User Manual
Page 5
![background image](/manuals/580105/5/background.png)
5
DeviceNet
Address
Switch Settings
6
z 1
DeviceNet
Address
Switch Settings
6
z 1
DeviceNet
Address
Switch Settings
6
z 1
DeviceNet
Address
Switch Settings
6
z 1
0
000000
16
010000
32
100000
48
110000
1
000001
17
010001
33
100001
49
110001
2
000010
18
010010
34
100010
50
110010
3
000011
19
010011
35
100011
51
110011
4
000100
20
010100
36
100100
52
110100
5
000101
21
010101
37
100101
53
110101
6
000110
22
010110
38
100110
54
110110
7
000111
23
010111
39
100111
55
110111
8
001000
24
011000
40
101000
56
111000
9
001001
25
011001
41
101001
57
111001
10
001010
26
011010
42
101010
58
111010
11
001011
27
011011
43
101011
59
111011
12
001100
28
011100
44
101100
60
111100
13
001101
29
011101
45
101101
61
111101
14
001110
30
011110
46
101110
62
111110
15
001111
31
011111
47
101111
63
111111
Setting the Data Rate
DIP switches 7 and 8 set the data rate at which the RediSTATION
communicates on the DeviceNet network. The factory default
setting is 125K BPS.
DeviceNet Data Rate
00 = 125K BPS
01 = 250K BPS
10 = 500K BPS
11 = Unused
Default Configuration
OFF = 0
ON = 1
10
1
2
3
4
5
6
7
8
9
The data rate determines the maximum length of the DeviceNet
cable.
Data Rate
Cable Length (Maximum)
125K BPS
500 meters (1600 feet)
250K BPS
200 meters (600 feet)
500K BPS
100 meters (300 feet)
To set the DeviceNet data rate:
1. Refer to the table above to select the correct data rate.
2. Slide switches 7 and 8 to the appropriate ON/OFF positions.