beautypg.com

Field wiring connections, Wire the modules – Rockwell Automation 2085-IA8_IM8_OA8 Micro800 8-Point Input and 8-Point Output AC Modules User Manual

Page 8

background image

8 Micro800 8-Point Input and 8-Point Output AC Modules

Publication 2085-IN005B-EN-P - September 2012

System Assembly

The Micro800 expansion I/O module is attached to the controller or another I/O module by
means of interconnecting latches and hooks, as well as the bus connector. The Micro850
controller and expansion I/O modules must terminate with a 2085-ECR Bus
Terminator module.

Be sure to lock the module interconnect latches and tighten the RTB hold down screws before
applying power to the module.

For installation of the 2085-ECR module, refer to Micro800 Bus Terminator Module
Installation Instructions, publication

2085-IN002

.

Field Wiring Connections

In solid-state control systems, grounding and wire routing helps limit the effects of noise due to
electromagnetic interference (EMI).

Wire the Modules

Included with your module is a single 12-pin Removable Terminal Block (RTB). Basic wiring of
the module is shown below.

ATTENTION: Failure to connect a bus terminator module to the last expansion I/O module will
result in a controller hard fault.

ATTENTION: Do not wire more than 2 conductors on any single terminal.