Environmental specifications – Rockwell Automation 2085-IA8_IM8_OA8 Micro800 8-Point Input and 8-Point Output AC Modules User Manual
Page 11

Micro800 8-Point Input and 8-Point Output AC Modules 11
Publication 2085-IN005B-EN-P - September 2012
Off-state voltage drop, max
1.5V AC @ 0.5 A
2.5V AC @10 mA
Fusing
Not protected. A suitable rating fuse is recommended to protect outputs.
Output signal delay
Off to On
On to Off
9.3 ms for 60 Hz, 11 ms for 50 Hz
9.3 ms for 60 Hz, 11 ms for 50 Hz
Surge current, max
5 A
Environmental Specifications
Attribute
Value
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…65 °C (-4…149 °F)
Temperature, surrounding air, max
65 °C (149 °F)
Temperature, non-operating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% non-condensing
Vibration
IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
25 g
Shock, non-operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
25 g – for DIN rail mount
35 g – for panel mount
Emissions
CISPR 11
Group 1, Class A
ESD immunity
IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity
IEC 61000-4-4:
±2 kV at 5 kHz on signal ports
Surge transient immunity
IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports
Conducted RF immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Output Specifications - 2085-OA8
Attribute
Value