General specifications – Rockwell Automation 2085-IA8_IM8_OA8 Micro800 8-Point Input and 8-Point Output AC Modules User Manual
Page 10
10 Micro800 8-Point Input and 8-Point Output AC Modules
Publication 2085-IN005B-EN-P - September 2012
Status indicators
8 yellow indicators
Isolation voltage
150V (continuous), Reinforced
Insulation Type, channel to
system
Type tested at 1950V DC for 60 s
240V (continuous), Reinforced Insulation Type, channel
to system
Type tested at 3250V DC for 60 s
North American temp code
T4
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines,
publication
(2)
RTB hold down screws should be tightened by hand. They should not be tightened using a power tool.
Input Specifications – 2005-IA8 and 2085-IM8
Attribute
2085-IA8
2085-IM8
Number of Inputs
8
Voltage category
120V AC
240V AC
Operating voltage range
74…120V AC
159…240V AC
Off-state voltage, max
20V AC
40V AC
Off-state current, max
2.5 mA
On-state current, min
5.0 mA @ 74V AC
4.0 mA @ 159V AC
On-state current, max
12.5 mA @ 120V AC
7.0 mA @ 240V AC
Input impedance, max
22.2 k
Ω
Inrush current, max
450 mA
Input filter time
Off to On
On to Off
≤
20 ms
IEC type compliance
Type 3
Output Specifications - 2085-OA8
Attribute
Value
Number of Outputs
8
Voltage category
120V/230V AC
Operating voltage range
120…240V AC
Output voltage, min
85V AC
Output voltage, max
240V AC
Off-state current, max
2.5 mA
On-state current, min
10 mA per output
On-state current, max
0.5 A per output
On-state current,
per module, max
4 A
General Specifications
Attribute
2085-IA8
2085-IM8
2085-OA8