beautypg.com

Making serial port connections, Or to connect a printer – Rockwell Automation 2711 MODBUS COMMUNICATIONS FOR PANELVIEW TERMINALS User Manual

Page 8

background image

Publication 2711-6.9 - March 2000

8 Modbus Communications for PanelView Terminals

Making Serial Port
Connections

Use the RS-232 serial port on the PanelView terminal to:

download/upload applications over a serial link

or to connect a printer

PanelView

9-pin male

Computer

9 to 25 Pin Adapter

(if required)

RS-232 Printer/

File Transfer Port

1

5

9

6

9-pin female

9-pin male

1
2
3
4
5
6
7
8
9

TXD (Data Transmit)

RXD (Data Receive)

COM

DTR

DSR
RTS

CTS

NC

DCD

PV550 Printer Port (DCE)

9-pin male

1
2
3
4
5
6
7
8
9

TXD or TX1 (Data Transmit)

RXD or TR1 (Data Receive)

COM
DSR (pulled high to +12V)

NC

RTS or RX2 (Data Receive)
CTS or TX2 (Data Transmit)

NC

NC

PV300/600/900/1000/1400 Printer Port (DCE)

1
2
3
4
5
6
7
8
9

TXD or TX1 (Data Transmit)

RXD or RX1 (Data Receive)

COM

DSR (pulled high to +12V)

NC

NC

CTS (pulled high to +12V)

NC

NC

Printer/Computer Port (DTE)

9-pin male

PV550 Printer Port (DCE)

1
2
3
4
5
6
7
8
9

TXD or TX1 (Data Transmit)

RXD or RX1 (Data Receive)

DSR (pulled high to +12V)

NC

NC

CTS (pulled high to +12V)

NC

NC

2
3 TXD or TX1 (Data Transmit)

RXD or RX1 (Data Receive)

9-pin

2
3
5

TXD COM

TXD (Data Transmit)

RXD (Data Receive)

Printer/Computer Port (DTE)

25-pin

2
7

3

5 COM

Upload/Download or Printer Cable without Hardware Handshaking

Available Cables

2711-NC13

5 m (16.4 ft)

2711-NC14

10 m (32.7 ft)

2706-NC13

3 m (10 ft)

1
2
3
4
5
6
7
8
9

1
2
3
4
5
6
7
8
9

Printer

9-pin female

RS-232

Port

COMM 1 or 2