Redundant Systems

Chapter 12

System Requirements

Most redundant systems must use at least these system components. For some
applications, the ControlNet and EtherNet/IP modules are optional.

Table 46 - System Requirements

Quantity

Item

Notes

2

ControlLogix chassis

Both chassis must be the same size.

2

ControlLogix power supply

Must be the same in each chassis.

2

ControlLogix controller

Use 1756-L6x or 1756-L7x controllers.
Use the same catalog number, series, firmware revision, and

memory size controllers in each chassis.

Same slot placement.

2

ControlLogix ControlNet
communication module

Use 1756-CN2/B, 1756-CN2R/B, or 1756-CN2RXT modules.
ControlNet modules in the chassis must be identical in firmware

revision, in series, slot placement, and module type.

2

ControlLogix EtherNet/IP
communication modules

Use the 1756-EN2T, 1756-EN2TXT, or 1756-EN2TR modules.
Must be identical in firmware revision, slot placement, and module

type.

2

Redundancy module

Use 1756-RM2 or 1756-RM2XT modules.
Redundancy modules in the chassis must be identical in firmware

revision and slot placement.

For L7x high performance systems, RM modules must be RM/B and

must have the same series and firmware revision in the chassis.

1 or 2

Redundancy module cable
(fiber-optic)

Use the 1756-RMCx cable.
Standard lengths are available.

2

Additional ControlNet nodes

Place all I/O in remote chassis or DIN rails.
Add at least two nodes to each ControlNet network and the

redundant chassis pair.

For enhanced redundancy, you must have at least one

keeper-capable ControlNet device at a node address lower than the
node addresses of the ControlNet modules in the redundant chassis.