Network status – Rockwell Automation 1734-8CFGDLX POINT I/O Module with 8 Configurable 24V DC Points and DeviceLogix IN User Manual

Page 21

background image

POINT I/O Module with 8 Configurable 24V DC Points and DeviceLogix 21

Publication

1734-IN039A-EN-P - March 2009

Network Status

Status

Description

Recommended action

Off

Device is not online.

- Device has not completed
dup_MAC_id test.

- Device not powered - check module
status indicator.

Apply power to device, wait for
dup_MAC_id to complete, and
correct, as needed.

Green

Device is online and has connections
in the established state.

None.

Flashing
green

Device is online but has no
connections in the established state.

None - device is in Idle or Program
mode.

Flashing red

One or more I/O connections in
timed-out state.

This could also mean a peer is not
producing data at all, or it is not
configured correctly.

Check I/O connection with master.
Verify peers are present and
configured properly.

Red

Critical link failure - failed
communication device. Device
detected error that prevents it
communicating on the network.

Verify that adapter and terminal
bases are properly installed, and
reinstall, as needed.

Flashing
red/green

Communication faulted device - the
device has detected a network
access error and is in communication
faulted state.

Device has received and accepted an
Identify Communication Faulted
Request - long protocol message.

Verify that adapter is properly
installed, and reinstall, as needed.