Network status – Rockwell Automation 1734-8CFGDLX POINT I/O Module with 8 Configurable 24V DC Points and DeviceLogix IN User Manual
Page 21
POINT I/O Module with 8 Configurable 24V DC Points and DeviceLogix 21
Publication
1734-IN039A-EN-P - March 2009
Network Status
Status
Description
Recommended action
Off
Device is not online.
- Device has not completed
dup_MAC_id test.
- Device not powered - check module
status indicator.
Apply power to device, wait for
dup_MAC_id to complete, and
correct, as needed.
Green
Device is online and has connections
in the established state.
None.
Flashing
green
Device is online but has no
connections in the established state.
None - device is in Idle or Program
mode.
Flashing red
One or more I/O connections in
timed-out state.
This could also mean a peer is not
producing data at all, or it is not
configured correctly.
Check I/O connection with master.
Verify peers are present and
configured properly.
Red
Critical link failure - failed
communication device. Device
detected error that prevents it
communicating on the network.
Verify that adapter and terminal
bases are properly installed, and
reinstall, as needed.
Flashing
red/green
Communication faulted device - the
device has detected a network
access error and is in communication
faulted state.
Device has received and accepted an
Identify Communication Faulted
Request - long protocol message.
Verify that adapter is properly
installed, and reinstall, as needed.